%0 Report %D 2011 %T Model-based controls for integrated shading and UFAD control: Report on initial studies %A Brian E. Coffey %A Eleanor S. Lee %K cloud computing %K integrated controls %K Model predictive control (MPC) %K offline optimization %K shading and HVAC controls %X

Methods and initial results are described for model-based controls with offline optimization for integrated shading and UFAD control for an office building in New York. Two cases are studied through lookup-table calculation and annual simulation of the resulting controllers: one case with interior blinds, the other case with exterior blinds. The interior blind case was found to reduce HVAC energy by 5% over a simple baseline control, and the exterior blind case produced a 5.6% HVAC energy savings over the baseline. Further investigations and case studies are planned.

%8 10/2011 %9 DOE/ CEC PIER Technical Report